UK Commercial Statutory Compliance Matrix
Inspect statutory review cycles, Dutyholder responsibilities, and British Standard deliverables prior to your next Fire & Rescue Service or BSR audit.
BS EN 12845 // HYDRAULICSprinkler Valve & Flow Telemetry
Weekly churn & quarterly flow proof
BS 5839-1 // ADDRESSABLEControl Panel & Loop Voltage
6-monthly cause-and-effect audit
BS 5266-1 // PHOTOMETRICEmergency Lighting 3-Hr Drain
Annual lux-meter escape route log
| Code / Standard | Statutory Requirement | Review Cycle | Deliverable | Status |
|---|---|---|---|---|
| RRO 2005 // Art. 9 | Suitable & Sufficient Fire Risk Assessment (PAS 79-1) All Non-Domestic & Common Parts · Responsible Person (Employer / Managing Agent) | Annual Review / Material Change | BAFE SP205 Certified FRA & Prioritised Action Plan | Mandatory |
| BSA 2022 // Part 4 | Golden Thread Digital Safety Case & Accountable Person Logs HRB 18m+ or 7+ Storeys (2+ Residential Units) · Principal Accountable Person (PAP) | Continuous / BSR Gateway Updates | Immutable Digital Safety Case & Resident Engagement Log | Critical |
| BS 5839-1:2017 | Commercial Fire Detection & Fire Alarm Servicing L1–L5 & M Commercial Categories · Responsible Person / Facilities Lead | 6-Monthly (Minimum) + Weekly User Call-Point Test | Cause-and-Effect Verification & FIA Inspection Certificate | Mandatory |
| BS 5266-1:2016 | Emergency Escape Lighting Duration & Lux Verification All Escape Routes, Open Areas & High-Risk Tasks · Dutyholder / Building Operations | Monthly Flick Test + Annual 3-Hour Drain Test | 3-Hour Full Duration Certificate & Lux Level Schedule | Statutory |
| BS EN 12845 / LPC | Automatic Sprinkler Pump Churn, Valve & Tank Diagnostics Commercial Warehousing, Retail & HRB Suppression · Building Owner / FM Contractor | Weekly Pump Test + Quarterly / Annual Hydraulic Audit | Pressure-Flow Curve & LPC Sprinkler Compliance Report | Critical |
| RRO 2005 // Art. 17 & Reg 10 | Fire Door & Passive Compartment Penetration Inspection FD30S / FD60S Doorsets & Service Risers · Responsible Person / Accountable Person | Quarterly (HRB Common Doors) / Annual (Commercial) | Pin-Indexed Door Schedule & Intumescent Seal Audit | Mandatory |
| BS 9999 / TR19 | Smoke Control, Dampers & Kitchen Extract Duct Hygiene Atriums, Basement Car Parks & Commercial Kitchens · Commercial Landlord / Catering Operator | Annual Damper Drop Test + 6-Monthly TR19 Clean | Airflow Velocity Log & BESA TR19 Grease Thickness Certificate | Statutory |